7
ambient temperature is below 50°F (38°F
for all other units with a Digital Control
Board), which is too low for the heater to
operate, or the unit is low on refrigerant.
Once the outside temperature has risen
above 60ºF, and the LP code remains, call
the factory for repair.
PSd: This code means there is a pool sensor
defect. Please call to arrange service for
the heat pump.
DSd: This code means there is a defrost
sensor defect. Please call to arrange
service for the heat pump.
LP3: This is like the “LP” described
above, however the unit has shut
down because this fault has happened
3 times within a 24 hour time period.
If the ambient temperature is below
50°F (38°F for all other units with a
digital control board), the problem will
most likely persist until the ambient air
temperature rises above 50°F. Pressing
any of the buttons on the front control
panel will restore the unit to its normal
operating mode. If the ambient air
temperature is not the issue and the
heat pump continues to display “LP” or
“LP3”, please call to arrange service for
the heat pump.
HP3: This is like the “HP” described
above, however the unit has shut down
because this fault has happened 3 times
within a 24 hour time period. Please
check your pool’s plumbing, valves and
pump / filter system for blockages or
flow restrictions, as this is most likely
the cause for the fault. Pressing any
of the buttons on the front control
panel will restore the unit to its normal
operating mode. If your pump and
filter system is working normally and
there are no flow restrictions and the
heat pump continues to display “HP”
or “HP3”, please call to arrange service
for the heat pump. Please note, we will
not be responsible for non-warranted
service calls.
FS: This code has the following
sequence:
• When rst displayed, the unit has
started the defrost cycle and will
reverse operation for 2 minutes. If
unit is at acceptable temperature
after the defrost cycle, it will go back
into heating mode.
• If coolant temperature is still too
low after the initial 2 minute
defrost cycle, unit will shut off the
compressor and run only the fan for
60 minutes. If unit is at acceptable
temperature after the 60 minutes, it
will go back into heating mode.
• If coolant has not reached the desired
temperature after the 60 minutes,
fan only mode, unit will shut down
and display “FS”.
• Unit will resume normal operation
after ambient temperature reaches
acceptable operating temperature.
MODELS: 1300h/c FS: If in “cooling-
mode”, this may indicate that there is not
enough water flow.
COL: This code reminds you that the
unit is running in the cooling mode.
LP: If in “cooling mode”, this code may
indicate that there is not enough water
flow
HP: If in “cooling mode”, this code may
indicate that an external coil is blocked
or that there is recirculated air.
HOT: This means the pool temperature has
increased by while the unit is operating
in theCOLmode. This is only a warning
that the unit is having difficulty cooling
the pool to the desired temperature. The
“HOT” message will remain until either
the pool drops to the desired temperature
or the set “COL” temperature is raised
above the pool’s current temperature.
MODELS: 1100E Series, 1300 Series
AND 1300H/C Series
FL3: This code means that water flow
was lost. Check the system for flow
obstructions.
Unit is not running (All Models):
• Check the power light. Check to see
if the breaker is set.
• Make sure the ltration system is on
• Make sure the thermostat is higher
than the pool water temperature
• Make sure the lter is clean and is
allowing enough water to flow
• Make sure the outside ambient
temperature is higher than 50ºF (3F
for all other units with a Digital Control
Board)
• Make sure the 5-minute time delay
has passed
• Make sure the 208/230 VAC
transformer is wired to match in
coming power levels.
FOR TCE UNITS
• Make sure time setting, in “FIL”
mode, is not set to “OFF”.
Unit is running but not heating:
• Check the air coming out of
the top of the unit. It should be
approximately 8ºF to 15ºF lower
than the surrounding ambient air
temperature. If not, call for service.
Unit is running but not cooling:
• After 5 minutes, Check the air coming
out of the top of the unit. It should
be approximately 8ºF to 15ºF higher
than the surrounding ambient air
temperature. If not, call for service
Unit will not cool:
FOR h/c UNITS:
• Make sure P-S is set to “POL” mode
as unit will not cool in “SPA” mode.
Unit runs continuously:
It may be running continuously
because it cannot reach the desired
temperature.
• Lower the temperature setting below
the pool water temperature. Unit
should turn off. If the unit is still
running, call for service.
• A pool blanket may be required to
help reach this temperature. Also, the
filter pump may need to run longer
for the heater to reach the desired
temperature.
FOR TCE UNITS
• Make sure the setting is not set to
“ON” position in the “FIL” mode.
Unit is cycling:
• Check the lters for proper water
flow
• Check the evaporator coil for severe
frost
• Unit could be low on refrigerant.
At this point, call for service and
turn off the power to the heater to
keep the cycling from damaging the
compressor.
Troubleshooting
Guide
(continued)